- Isolator included, with lock
- Provides reliable early warning of a Fire condition upon reaching a rate of rise of the temperature or fixed temperature threshold in the protected premises.
- The fire detector is suitable for premises with normal ambient temperature, without possible sudden changes. Supply voltage: (15-30)VDC
- Terminals: For wires with cross section (0.8-2.5)mm2
- Degree of protection: IP 43
- Operation temperature: - 10°C to 55°C
- Relative humidity: (93±3) % at 40°C
- Sensitivity: In accordance with EN54-5, class A1S, A2S or BS
- Mounting: Using base type 7100
- Casing material: ABS plastics, white
- Protected area: Circle with diameter 10m, h 8m
DGAFD7120