- General
- Cells per unit6
- Voltage per unit12V
- Nominal Capacity70W@15min-rate to 1.67V per cell @25C
- Weight5.35 kg (± 5%)
- Internal resistance≤ 12 mΩ
- TerminalF13-BP(M5)
- Max. discharge current180A (5 sec)
- Short circuit current860A
- Design life8 years
- Max. charging current5.4A
- Reference capacityC10 17.0Ah C20 18.0Ah
- Standby use capacity13.7V~13.9V @ 25°C Temperature Compensation: -3mV/'C/Cell
- Cycle use voltage14.6 V~14.8V @ 25°C Temperature Compensation: -4mV/°C/Cell
- Operating temperature rangeDischarge: -20'C~60C Charge: 0°C~50C Storage: -20'C~60°C
- Normal operating temperature range25C+5C
- Self dischargeRITAR Valve Regulated Lead Acid (VRLA) batteries can be stored for up to 6 months at 25°C and then recharging is recommended. Monthly Self-discharge ratio is less. than 3% at 25'C Please charge batteries before using
- Container materialA.B.S. UL94-HB, UL94-V0 Optional